In a home, a 30 mA RCD is required for socket-outlets rated up to 32 A, for new or significantly altered lighting circuits and for cables concealed in walls or ceilings. That covers most circuits on a modern board. It does not mean an older board has to be thrown out just because it has no RCD: Electrical Safety First says a consumer unit need not be replaced for that reason alone, and describes a missing RCD as an improvement recommended (C3), not an emergency.
This guide reflects the Institution of Engineering and Technology (IET), NAPIT, Electrical Safety First, BSI and GOV.UK pages opened on 3 November 2026. It is written for homes in Cirencester and the Cotswolds, England, and is general information, not a check of your installation. If you want your own board looked at, describe it to Jack or see JI Electrical’s consumer unit assessment page.
What an RCD does and what it does not
The IET says RCDs are required to protect people from electric shock, and that most domestic circuits need RCD protection. An RCD watches for current leaking where it should not, for example through a person, and cuts the supply. It is not an overload device. Overload protection comes from the fuse or circuit-breaker on each circuit, which is why a guide that says an RCD trips when you plug in too many appliances has the two mixed up.
The unit itself is also covered by a separate rule. The IET says that from January 2016 the Wiring Regulations required domestic consumer units to be made from non-combustible material, to contain any fire inside the enclosure. That is about the box, not the RCDs, and it is one reason a plastic board from before 2016 may be worth an assessment.
Which circuits need RCD protection
The table sets out what the opened sources say, circuit by circuit, with the regulation number where a source gives one. The BS 7671 text itself is paywalled and was not opened, so regulation numbers appear only as the sources quote them.
| Circuit or situation | What the sources say | Source |
|---|---|---|
| Socket-outlets rated up to 32 A | A 30 mA RCD is required (Regulation 411.3.3). This applies where ordinary people, children or disabled people are likely to use them | IET Wiring Matters |
| New or significantly altered lighting circuits in a home | Additional protection by a 30 mA RCD (Regulation 411.3.4) | IET consumer units FAQ |
| Cables concealed in walls or ceilings | Additional RCD protection where the current standard requires it (Regulations 522.6.201 to 203) | Electrical Safety First guide summary |
| Mobile equipment up to 32 A used outdoors | A 30 mA RCD is required (Regulation 411.3.3) | IET Wiring Matters |
| An existing board with no RCD | Need not be replaced for that reason alone. Listed as a C3, improvement recommended | Electrical Safety First |
| Every socket, as a recommendation | Note 3 to the regulation recommends RCD protection of all socket-outlets. It is guidance, not the mandatory test | IET Wiring Matters |
Two things in the table are worth pausing on. First, the lighting rule is Regulation 411.3.4, and the IET FAQ applies it to new lighting circuits and to existing circuits that are significantly altered in a home. Some trade blogs cite 411.3.4 as the rule that puts every circuit behind an RCD, which is not what the IET page says. Second, the socket rule has a documented risk assessment exception, but the IET says it applies only to the “other locations” case, not to places ordinary people, children or disabled people use. A home is the first case, so the exception does not help a householder.

So does every circuit need one?
None of the sources opened says “every circuit” in those words. What they say is narrower and easier to check: sockets, lighting that is new or altered, and cables concealed in walls or ceilings. In a typical house those three triggers leave few final circuits outside them. That is our reading of the sources, not a quoted rule, and the position for your design is something an electrician confirms from the circuits actually installed.
Do I have to replace an older board?
Not automatically. Electrical Safety First’s best practice guide, summarised on Voltimum in 2016, says a consumer unit need not be replaced just because it has rewireable fuses, cartridge fuses or older circuit-breakers, or because it lacks RCD protection. That guide was written before the 2022 amendment, so treat it as a statement of the principle rather than a current regulation list. The guide also says a unit that has been damaged or has overheated usually needs immediate replacement, and that a contractor should first encourage an Electrical Installation Condition Report (EICR) before a planned replacement.
Electrical Safety First’s question page puts the same point in report terms. A fusebox without RCD protection is a C3, improvement recommended, which is not urgent, and the page suggests considering an upgrade to the latest standard. If you let property, a C3 on its own is not the same as a C1 or C2, so see what the EICR codes mean, what happens after a failed EICR and the landlord EICR guide. For signs that a board needs attention, read seven reasons to assess a fuse box.
Single RCD, two RCDs or one per circuit
The regulation tells you which circuits need protection. It does not tell you how to arrange the devices. The three common layouts are below, using what the sources say and nothing about price.
| Layout | How it works | What the sources say |
|---|---|---|
| Two RCDs (split load) | Each RCD protects a group of circuits | The IET says this is the usual arrangement, so one tripping leaves the other group powered |
| One RCD for everything | A single device protects all the circuits that need it | Electrical Safety First says circuits needing RCD protection must be divided across enough RCDs to avoid hazards and minimise inconvenience (Regulations 314.1 and 314.2) |
| An RCBO on each circuit | Each circuit has its own combined RCD and circuit-breaker | A fault takes out one circuit. The opened sources describe the arrangement but give no regulation that requires it |
The sources do not rank these, and neither will this guide. What the regulations ask for is that a trip does not cause a hazard or needless disruption, so the practical question for you is how much of the house you are happy to lose when one appliance fails. An all-RCBO board costs more than a split-load board, and our consumer unit replacement cost guide gives attributed market ranges with the VAT basis. This guide quotes no JI Electrical price.
Before you accept a quote
Ask which protection each circuit gets.
A good quote names the board layout and which circuits sit behind which RCD or RCBO.
Ask for a quoteCall 07380 944864
Which edition of the regulations applies
NAPIT’s overview says BS 7671:2018+A2:2022 was available from 28 March 2022, and that its requirements could not be mixed with the earlier version. BSI now lists BS 7671:2018+A4:2026, released in April 2026, which incorporates Amendment 3 of 2024 and, in BSI’s words, adds a chapter on stationary secondary batteries, new sections on functional earthing for ICT equipment and on Power over Ethernet, and a major revision of the medical locations section. BSI gives 15 October 2026 as the withdrawal date of the previous A2+A3 edition.
None of the headline changes BSI lists is about domestic RCD rules, but a headline list is not the full amendment, and the regulation text was not opened. So the useful question is a simple one: ask which edition your new board is designed and certified to. The edition should appear on the certificate. On arc fault detection, NAPIT says the 2022 amendment makes the devices required in some higher-risk residential buildings and recommended for socket circuits in other premises, so a standard home is in the recommended group, not the required one.

Who can do the work and what you get
GOV.UK lists replacing fuse boxes and connected electrics among alteration projects that may need building regulations approval. It says you do not need to get approval yourself if you use someone registered with a competent person scheme, and that you should check with a building control body if you are unsure. Our Part P guide sets out which jobs must be notified, and the certificates guide explains what paperwork to keep. Electrical Safety First’s guide says a new installation needs an Electrical Installation Certificate with test schedules, and that existing defects that are not dangerous should be recorded on it. This guide makes no claim about which scheme JI Electrical belongs to.
Questions to put to anyone quoting for a board
- 1Which circuits sit behind which device?
Ask for the layout in writing: two RCDs, one RCD or an RCBO per circuit.
- 2Which edition is it designed to?
Ask for the edition and amendment to be named on the certificate.
- 3Is the enclosure non-combustible?
The IET says domestic units have needed to be since January 2016.
- 4Will you test the existing installation first?
Electrical Safety First says an EICR should be encouraged before a planned replacement, and that defects must be recorded.
- 5What certificate and test schedule do I get?
Ask what is handed over, and how the work is notified for building regulations.
- 6What is excluded from the price?
Ask about making good, repairs found during testing and VAT. Our consumer unit upgrade guide lists what a quotation should include.
After the new board goes in
The IET says RCDs should be tested every six months by pressing the button marked T or Test, and that the device should switch off. If it does not, Electrical Safety First says to get a registered electrician to investigate. If the board then starts dropping a switch, read why electrics keep tripping before resetting it repeatedly. Planning an EV charger or other new load? See whether an EV charger needs a new consumer unit. Choosing who does the job is covered in seven checks for choosing an electrician in Cirencester, and the services page lists what JI Electrical offers. To discuss your own board, ask Jack directly.
Customer reviews
What customers say about Jack
Jack did a great job installing new spotlights in our kitchen. He turned up on time, worked efficiently, and everything was finished to a really high standard.
Jack and his colleague Freddie arrived on time, worked efficiently, and everything was completed to a really high standard. The price was fair and they left everything clean and tidy afterwards.
I contacted JI Eletrical within 24hrs with an issue and they came to fix it quickly and not had a problem since!
Consumer unit RCD questions
Does every circuit in my home need an RCD?
None of the sources opened for this guide says so in those words. The IET says a 30 mA RCD is required for socket-outlets up to 32 A and, in domestic premises, for new or significantly altered lighting circuits. Electrical Safety First's summary also lists cables concealed in walls or ceilings. Between them these cover most circuits in a home, so an electrician will confirm the position for your design.
Must I replace an old fuse box that has no RCD?
Not automatically. Electrical Safety First's guidance says a consumer unit need not be replaced just because it has rewireable fuses or lacks RCD protection. Its question page describes a fusebox without RCD protection as a C3, improvement recommended, and suggests upgrading to the latest standard.
Is a dual RCD board still allowed?
The IET describes two RCDs, each protecting a group of circuits, as the usual arrangement, so that one tripping leaves the other group powered. Electrical Safety First says circuits needing RCD protection must be divided across enough RCDs to avoid hazards and minimise inconvenience. An all-RCBO board gives each circuit its own protection. Ask Jack which he recommends for your home.
Does an RCD protect against overload?
No. The IET describes RCDs as protection from electric shock, and Electrical Safety First links a tripping RCD to a fault in an appliance or wiring. Overload protection comes from the circuit-breaker or fuse on each circuit.
Which edition of the wiring regulations applies now?
BS 7671:2018+A2:2022 was available from 28 March 2022. BSI lists BS 7671:2018+A4:2026, released in April 2026, and gives 15 October 2026 as the withdrawal date of the previous A2+A3 edition. The headline changes BSI lists do not mention domestic RCD rules, but ask your electrician which edition your new board is designed to.
Does replacing a consumer unit need building regulations approval?
GOV.UK lists replacing fuse boxes and connected electrics among alteration projects that may need building regulations approval, and says you do not need to get approval yourself if you use someone registered with a competent person scheme. If unsure, GOV.UK advises checking with a building control body.
Sources checked on 3 November 2026
Each page below was opened on the day. None gives a JI Electrical price, and the BS 7671 text itself was not opened.
- IET Wiring Matters: socket outlets must be protected by a 30 mA RCD
- IET: consumer units, consumer guidance
- IET: consumer units and protective devices FAQs
- NAPIT: significant changes to BS 7671:2018+A2:2022
- Electrical Safety First: replacing a consumer unit, domestic and similar installations (Voltimum, 2016)
- Electrical Safety First: if my RCD keeps tripping
- BSI: BS 7671:2018+A4:2026 listing
- GOV.UK: building regulations approval, electrical work